    Technical Documents

  • Download .pdf document of this GFCI requirement page which shows the dates and locations for which ground-fault circuit interupter (GFCI) protection was required by the National Electrical Code (NEC) for Dwelling Units








  • Compiled by Jerry Peck © Copyright 1996-2008 Jerry Peck
    DWELLING UNIT
    120 volt GFCI Protected Receptacle Outlets - REQUIRED LOCATIONS
    DATE
    OF
    NEC
    EDITION
    S
    W
    I
    M
    M
    I
    N
    G
    P
    O
    O
    L
    S
    S
    P
    A
    S
    E
    X
    T
    E
    R
    I
    0
    R
    B
    A
    T
    H
    R
    O
    O
    M
    S
    G
    A
    R
    A
    G
    E
    H
    Y
    D
    R
    O
    M
    A
    S
    S
    A
    G
    E
    B
    O
    A
    T
    H
    O
    U
    S
    E
    S
    K
    I
    T
    C
    H
    E
    N
    U
    N
    F
    I
    N
    I
    S
    H
    E
    D
    B
    A
    S
    E
    M
    E
    N
    T
    S
    C
    R
    A
    W
    L
    S
    P
    A
    C
    E
    W
    E
    T

    B
    A
    R
    L
    A
    U
    N
    D
    R
    Y
    U
    T
    I
    L
    I
    T
    Y
    H
    O
    T
    T
    U
    B
    S
    T
    U
    B
    S
    1971
    X1b
    -
    X2
    -
    -
    -
    -
    -
    -
    -
    -
    -
    1975
    X1a
    -
    X
    X
    -
    -
    -
    -
    -
    -
    -
    -
    1978
    X1a
    -
    X3a
    X
    X4
    -
    -
    -
    -
    -
    -
    -
    1981
    X1a
    X5a
    X3a
    X
    X4
    -
    -
    -
    -
    -
    -
    -
    1984
    X1b
    X5a
    X3a
    X
    X4
    -
    -
    -
    -
    -
    -
    -
    1987
    X1b
    X5a,b
    X3a
    X
    X4
    X5b
    X
    X6a
    X7a
    -
    -
    -
    1990
    X1b
    X5a,b
    X3a
    X
    X4
    X5b
    X
    X6a
    X7b
    X
    -
    -
    1993
    X1b
    X5a,b
    X3a
    X
    X4
    X5b
    X
    X6a
    X7b
    X
    X8
    -
    1996
    X1c
    X5a,b
    X3b
    X
    X4,9a
    X5b
    X
    X6b
    X7b,c
    X
    X8
    -
    1999
    X1c
    X5a,b
    X3b
    X
    X4,9b
    X12a
    X
    X6b
    X7b,c
    X
    X8
    -
    2002
    X1c
    X5a,b
    X3b
    X
    X4,9b
    X12a
    X
    X6b
    X7b,c
    X
    X8
    -
    2005
    X1c
    X5a,b
    X3b
    X
    X4,9b
    X12a
    X
    X6b
    X7c,d
    X
    X11
    X11
    2008
    X1d
    X5a,c
    X3b
    X
    X
    X12b
    X
    X6c
    X7e
    X
    X11
    X11

    • X1a. All receptacles outlets within 15 feet of the water, in any direction (also see EXTERIOR), NO receptacle outlets within 10 feet of inside of pool walls.


    • X1b. All receptacles outlets within 20 feet of the water, in any direction (also see EXTERIOR), NO receptacle outlets within 10 feet of inside of pool walls.


    • X1c. All receptacles outlets within 20 feet of the water, in any direction (also see EXTERIOR), NO receptacle outlets within 10 feet of inside of pool walls, except receptacles for pump which mus be at least 5 feet from of inside of pool walls.


    • X1d. All receptacles outlets within 20 feet of the water, in any direction (also see EXTERIOR), NO receptacle outlets within 6 feet of inside of pool walls, including receptacles for pump.


    • X2. Effective January 1, 1973.


    • X3a. Changed to ‘with direct grade access to dwelling and outlets’ in 1978. Direct grade access was defined in 1987 as 6 feet 6 inches or less above grade.


    • X3b. Changed back to ALL dwelling unit exterior outlets in 1996; except an outlet for snow melting equipment IF on a dedicated circuit and NOT readily accessible.


    • X4. All, except outlets not readily accessible (6 feet 8 inches? or higher) and outlets for dedicated appliances which are not easily movable (freezer, refrigerator, etc.).


    • X5a. Outdoor spa or hot tub - see Swimming Pools.


    • X5b. Indoor spa or hot tub, receptacles within 10 feet, receptacles must be at least 5 feet from inside wall of spa.


    • X5c. Indoor spa or hot tub, receptacles within 10 feet, NO receptacle outlets within 6 feet of inside of spa or hot tub walls.


    • X6a. Outlets within 6 feet of kitchen sink to serve as counter top outlets, outlets not to be installed face up in work surfaces and counter tops.


    • X6b. All outlets which serve as counter top outlets, except outlets for refrigerator or freezer.


    • X6c. All outlets which serve as counter top outlets.


    • X7a. At least one, which must be identified as being GFCI protected.


    • X7b. Changed to all receptacles in unfinished basements and crawl spaces, except: laundry, sump pump, refrigerator or freezer.


    • X7c. Except where not readily accessible.


    • X7d. Changed to all receptacles in unfinished basements, except: laundry appliances, refrigerator or freezer, or permanently installed burglar or fire alarm.


    • X7e. Changed to all receptacles in unfinished basements, except permanently installed burglar or fire alarm.


    • X8. Outlets within 6 feet of wet bar sink to serve as counter top outlets, outlets not to be installed face up in work surfaces and counter tops.


    • X9a. Unfinished accessory buildings are treated like garage.


    • X9b. Accessory buildings that have a floor located at or below grade and not intended as habitable rooms and limited to storage areas, work areas, and areas of similar use.


    • X10. Receptacles within 5 feet.


    • X11. Outlets within 6 feet of sink.


    • X12a. Outlets serving hydromassage tub. All 125-volt 30 amp and less outlets withing 5 feet horizontally from inside walls of hydromassage tub.


    • X12b. Outlets serving hydromassage tub. All 125-volt 30 amp and less outlets withing 6 feet horizontally from inside walls of hydromassage tub.


    • IT IS BEST TO INSTALL GFCI PROTECTION TO MEET, THE MOST CURRENT CODE, ALL WET AREAS, AREAS SUBJECT TO BECOMING WET, AND AREAS OF POTENTIAL ELECTRICAL SHOCK.



    © Copyright 2008 JerryPeck